76 
 
frequency.     
Maximum Carrier Frequency 
Minimum Carrier Frequency 
Carrier Frequency Proportional Gain     
<1> This setting is only enabled when C6-00=0.   
□  Setting a Fixed Carrier Frequency   
C6-01 can be adjusted within the setting range when C6-00 is set to 0.   
Set the same value in C6-01 and C6-02 in control methods other than V/F Control.     
□  Setting a Variable Carrier Frequency (Only for V/F Control) 
In V/F Control, the carrier frequency can be set up to change linearly with the output frequency 
by setting C6-01, C6-02 and C6-03 as shown in Figure 6.33. 
 
Carrier Frequency
C6-01
Output Frequency 
╳ C6-03
Output 
Frequency
d1-02
Maximum Output Frequency
 
Figure 6.33 Carrier Frequency Changes Based on Output Frequency 
Note:   
1. When C6-03>27 and C6-01<  C6-02 , the carrier frequency will be fixed to the value set to C6-01. 
2. When C6-03<7, C6-02 is disabled and the carrier frequency will be fixed to the value set to C6-01.   
  C6-04  Retain   
□  Carrier Frequency Changes Based on Rated Current 
According to carrier frequency settings, the drive rated output  current changes as shown in 
Table 6.11. The carrier frequency changes linearly with output current. Refer to Table 6.11 to 
calculate the value if it is not specified.   
 
Table 6.11 Carrier Frequency Changes Based on Rated Current