40
Reverse Rotation
Selection
0: Reverse Rotation Enabled
Drive accepts a run command of both
forward and reverse directions
1: Reverse Rotation disabled
Drive can accept only run command of
forward direction
Run Command
Action after Switch
0: Ignore Active Run Command at the New
Source
If a Run command at the new source is active,
the drive will not start or the drive will stop
operation if it was running when switching from
the old source to the new source. The drive can
start only when the Run command is removed
and given again.
1∶ Accept Active Run Command at the New
Source
If a run command at the new source is active,
the drive will accept it and run the motor
immediately right after switching from the old
source to the new source.
Run Command
Selection during
Programming
0
∶
Run command disabled during Programming
1
∶
Run command enabled during Programming
2
∶
Prohibit programming during run
The programming mode cannot be
displayed during run except for monitoring
parameter Group U.
Default∶ 0
Range: 0, 1, 2
Frequency
Command
Selection 2
0∶ Keypad
1∶ Control Circuit Terminal (Analog Input)
2∶ Terminal Up/Down
3∶ Modbus Communication
Default∶ 0
Min.: 0
Max.: 4
Frequency
superposition
Selection
Determines to accept or ignore an active Run
command from Remote during power up.
0∶ Ignore
Drive ignores an active run command during
power up
1∶ Accept
Drive accepts an active run command at power
up and runs the motor immediately.