Grid and EPS output terminals show as below:
Back shell Cable nut Threaded sleeve Connection terminal
• The grid voltage and frequency must be in the permissible range.
• An external AC breaker must be installed on the AC side of each inverter to
ensure that the inverter can be safely disconnected from grid when necessary.
• In the systems with multiple inverters, protect each inverter with a separate circuit
breaker.
• Never connect a load between the inverter and the circuit breaker.
Suggested cable requirement for Grid wires
Wiring Connection Procedure
Step1: Assembling the GRID Connector
•
Uninstall the AC terminals.
•
Remove an appropriate length of the jacket and insulation layer from the AC output
cable using a wire stripper.
•
Thread cables through back shell, cable nut, threaded sleeve in sequence, insert
cables into connection terminal according to polarities indicates on it and tighten
the screws.
•
Make sure Live/Neutral/PE wire are correct, please follow the markings on the
connector.
•
Push sleeve on to connection terminal until both are locked tightly.