Grid and EPS output terminals show as below:
Back shell Cable nut Threaded sleeve Connection terminal
WARNING
The grid voltage and frequency must be in the permissible range.
An external AC breaker must be installed on the AC side of each inverter to
ensure that the inverter can be safely disconnected from grid when necessary.
In the systems with multiple inverters, protect each inverter with a separate circuit
breaker.
Never connect a load between the inverter and the circuit breaker.
Suggested cable requirement for Grid wires
Model
Wire Size
Cable
Beaker
3~5KVA
12AWG
4-6mm²
32A
Wiring Connection Procedure
Step1: Assembling the GRID Connector
Uninstall the AC terminals.
Remove an appropriate length of the jacket and insulation layer from the AC output
cable using a wire stripper.
Thread cables through back shell, cable nut, threaded sleeve in sequence, insert
cables into connection terminal according to polarities indicates on it and tighten
the screws.
Make sure Live/Neutral/PE wire are correct, please follow the markings on the
connector.
Push sleeve on to connection terminal until both are locked tightly.