EasyManuals Logo

LMI Technologies Liquitron DP5000-1A User Manual

LMI Technologies Liquitron DP5000-1A
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
12
4.1.2 On / Off Mode
For ‘ON/OFF’ controllers with relay outputs (instead of pulse outputs) each pump is programmed as follows:
Set points 1 and 2 must be separated by 0.5 pH minimum. If ‘Point 3’ is selected in the Advanced Features Menu,
the user will be prompted to enter a pH value for Set Point 3 and a Pump Speed at Set Point 3. Set points 1 and 3,
2 and 3 must be separated by 0.1 pH minimum.
(6) ...... Press to increase/decrease the pH for Set Point 2.
(7) ...... Press again.
(8) ...... Press
to increase/decrease pump speed (pulse/min)
for Set Point 2.
‘Pump B’ (Base Pump) is programmed in a similar way.
Pump A Control Profile
(1) ...... Press ....to display Set Point.
(2) ...... Press
to increase/decrease pH Set Point.
(3) ...... Press
to save programmed Set Point.
(4) ...... Press
to programpH (Hysteresis) period for
relay. In this example, ‘Pump A’ will turn on at a pH of
8.0 (set point +pH). ‘Pump A’ will turn off when pH
drops to 7.5.
‘Pump B’ (Base Pump) is programmed in a similar way.
Controller must be in ‘OFF’ mode to program changes.
Hysteresis values can be set as low as 0.1 pH
Lowest setpoint value for pump B is 1pH
Highest setpoint value for pump B is 12 pH
Lowest setpoint value for pump A is 2 pH
Highest setpoint value for pump A is 13 pH
(866) 433-6682 • (281) 359-8538 • sales@novatech-usa.com • www.novatech-usa.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LMI Technologies Liquitron DP5000-1A and is the answer not in the manual?

LMI Technologies Liquitron DP5000-1A Specifications

General IconGeneral
BrandLMI Technologies
ModelLiquitron DP5000-1A
CategoryController
LanguageEnglish

Related product manuals