Chapter 7. Usage of Various Functions
7-108
9) Return to origin (POSORG)
Function block Description
Input
REQ : Execute POSORG function block
CH: Sets the channel (0 ~ 1)
HSC_CH: Sets POSORG input channel (0~3)
SCALE: Sets the scale (0 ~ 100%)
Output
DONE: Turns On after the function block is executed without error, and
turns Off if an error occurs or there is no execution command.
STAT: Displays error status
(1) Functions
When input condition turns on, corresponding origin return operation starts (Rising edge trigger)
After operation, current address is preset to designated origin address.
(2) Example program
When input condition(%MX000) turns on, Ch. 0 operates return to origin function to the DIR (designated direction).
After return to origin operation, the position address becomes 0 (ADDR designated value).