Chapter 6. Input and Output Specifications
6-17
6.3.5 Expansion module (TR output)
1) Specifications
Digital I/O module
Model
Specifications
G7E-TR10A
Output point 10 points
Insulation method Photo coupler insulation
Rated load voltage/current DC12V//24V
Operating load voltage range DC10.2 ~ 26.4V
Max. load current 0.5A/1 point, 4A/1COM
Off leakage current 0.1mA or lower
Max. inrush current 4A/10ms or lower
Max. voltage drop when on DC 1.5V or lower
Surge absorber Clamp diode
Off On 2 ms or lower
Response time
On Off 2 ms or lower
Common 10 points/COM
Operation indicator LED is on at on status of output
REMARK
1) Refer to 7.2 ‘Special Functions’ for the special modules
DC12/24V