Chapter 6. Input and Output Specifications
6-7
6.3 Digital Output Specifications
6.3.1 Main unit (Relay output)
1) Specifications
(1) Standard type
Main Unit
Model
Specifications
G7M-DR20U(/DC),
G7M-DRT20U(N)(/DC)
G7M-DR30U(/DC),
G7M-DRT30U(N)(/DC)
G7M-DR40U(/DC),
G7M-DRT40U(N)(/DC)
G7M-DR60U(/DC),
G7M-DRT60U(N)(/DC)
Output point 8 points, 4 points 12 points, 8 points 16 points, 12 points 24 points, 20 points
Insulation method Relay insulation
Rated load voltage/current
DC24V / 2A (r/load), AC220V / 2A (COS Ψ = 1)/1 point , 5A / 1COM
Min. load Voltage/current DC5V / 1mA
Max. load voltage/current AC250V, DC110V
Off leakage current 0.1mA (AC220V, 60Hz)
Max. On/off frequency 1,200 times/hr
Surge absorber None
Mechanical
More than 20,000,000
Rated on/off voltage/current load 100,000 or more
AC200V / 1.5A, AC240V / 1A (COSΨ = 0.7) 100,000 or more
AC200V / 1A, AC240V / 0.5A (COSΨ = 0.35) 100,000 or more
Life
Electrical
DC24V / 1A, DC100V / 0.1A (L / R = 7ms) 100,000 or more
Off On 10 ms or lower Response
time
On Off 12 ms or lower
Operation indicator LED is on at on status of output
2) Circuit diagram
L
Internal
circuit
COM
L
Relay