Chapter 7. Usage of Various Functions
7-6
(3) Program example
When the input condition %MX000 turns On, the CH 0 is enabled following the set mode.
When the present value becomes 8,333,777, %Q0.0.0 turns On.
The present values are saved in Current_Value.
- For the additional settings, refer to the section Chapter 8. High Speed Counter ‘Parameter
settings’.
8) High speed counter parameter settings
(1) Format setting
(a) Linear counter
If HSC is designate as Linear counter, it can counts from -2,147,483,648 to 2,147,483,647.
When the counter value reaches 2,147,483,647, CY output is set for the next pulse input, and the counter stops.
When the counter value reaches -2,147,483,648, BORR output is set for the next pulse input, and the counter stops.
REMAR