11. Monitoring
11-5
SV-iC5
11.4 Analog Output
Group LED Display
Parameter Name
Set
value
Min/Max
range
Factory
default
Unit
I/O group
I50
[Analog output item
select]
- 0/3 0
I51
[Analog output level
adjustment]
- 10/200 100 %
Output item and the level from the AM terminal are selectable and adjustable.
I50 : The selected item will be output to Analog output terminal (AM).
I50 Analog output
item select
10V
0 Output frequency. Max Frequency (F21)
1 Output current 150% of Inverter rated current
2 Output voltage 282 Vac
3
Inverter DC link
voltage
400 Vdc
I51 : If you want to use Analog output value as a gauge input , the value can be adjustable
corresponding to various gauge specifications.
AM
CM
0 ~ 10Vdc
Fault type
Operating status
when a fault
occurs