4. Basic configuration
4-2
SV-iC5
4.2 Recommended MCCB, Earth leakage circuit breaker (ELB) and Magnetic contactor specification
Model MCCB/
ELB(LS)
Magnetic
Contactor
Note
004iC5-1, 1F ABS33b, EBS333 GMC-12
008iC5-1, 1F ABS33b, EBS333 GMC-18
015iC5-1, 1F ABS33b, EBS333 GMC-25
022iC5-1, 1F ABS33b, EBS333 GMC-32
4.3 Recommendable AC/DC Reactor
Model AC input fuse AC reactor DC reactor
004iC5-1, 1F 10A 2.13mH, 5.7A 7.00mH, 5.4A
008iC5-1, 1F 20A 1.20mH, 10A 4.05mH, 9.2A
015iC5-1, 1F 30A 0.88mH, 14A 2.92mH, 13 A
022iC5-1, 1F 40A 0.56mH, 20A 1.98mH, 19 A