G. Installation
Installation of fixed type
Securely install the left and right mounting frames with M12 bolts (4ea).
1. Fixed type
Installation of draw-out type
Install draw-out type according to the instruction given below.
1. Securely install the cradle at the bottom with M12 bolts (4EA).
2. Pull the extension rails of cradle forward.
3. Put the breaker on the rail as shown in picture by using lifting device.
4. Please check if the circuit breaker fits well to the cradle.
5. Slowly push the circuit breaker by moving the rail handle.
2. Draw-out type
4(6) -M12
C
(Cradle rail)
B
(ACB mold frame)
A
(Cradle rail)
<Torque>
40~50 Nm
4(6)-M12
18