Manual charging
1. Charge the handle 7~ 8 times with full strokes.
2. When the closing spring is completely charged, the charging indicator shows “CHARGED”.
Manual closing
1. Push ON button.
2. The breaker will be closed.
3. The CLOSED/OPEN indicator shows “CLOSED” and the charging indicator shows “DISCHARGED”.
Caution : Before opening or closing the breaker equipped with an under voltage tripping device,
control voltage should be applied. Please operate only in the disconnected position.
Manual tripping
1. Push the OFF button and breaker will be tripped.
2. The CLOSED/OPEN indicator shows “OPEN”.
H. Operation
1. Manual operation
Charge
handle
ACB off and charged