■ Manual charging
1. Charge the handle 7~ 8 times with full strokes.
2. When the closing spring is completely charged, the charging indicator shows “CHARGED”.
■ Manual closing
1. Push ON button.
2. The breaker will be closed.
3. The CLOSED/OPEN indicator shows “CLOSED” and the charging indicator shows “DISCHARGED”.
Caution : Before opening or closing the breaker equipped with an under voltage tripping device,
control voltage should be applied. Please operate only in the disconnected position.
■ Manual tripping
1. Push the OFF button and breaker will be tripped.
2. The CLOSED/OPEN indicator shows “OPEN”.
H. Operation
1. Manual operation
Charge
handle
ACB off and charged
20