I. Trip unit externals and configuration
N, A type Knob Configuration
P,S type Knob Configuration
No Type of knob Mode setting step
Long-time current setting Ir
(0.4-0.5-0.6-0.7-0.8-0.9-1.0) × In
Long-time tripping delay tr (0.5-1-2-4-8-12-16-20-off), sec
@ 6 Ir
Short-time current setting Is
(1.5-2-3-4-5-6-8-10-off)× Ir
Short-time tripping delay tsd t off : (0.05-0.1-0.2-0.3-0.4), sec
t on : (0.1-0.2-0.3-0.4) , sec
Instantaneous pick-up Ii
(2-3-4-6-8-10-12-15-off)× In
Ground-fault pick-up Ig
(0.2-0.3-0.4-0.5-0.6-0.7-0.8-1-off)× In
Ground-fault tripping delay tg t off : (0.05-0.1-0.2-0.3-0.4)
t on : (0.1-0.2-0.3-0.4)
P, S type knob information
N, A type knob information
4. 온도 센서
1. Knob setting
No Type of knob Mode setting step
Continues current setting Iu
(0.5-0.6-0.7-0.8-0.9-1.0) × In
Long-time current setting Ir
(0.8-0.83-0.85-0.88-0.89-0.9-0.93-0.95-0.98-1.0) × Iu
Long-time tripping delay tr (0.5-1-2-4-8-12-16-20-off), sec
@ 6 Ir
Short-time current Setting Is
(1.5-2-3-4-5-6-8-10-off)× Ir
Short-time tripping delay tsd t off : (0.05-0.1-0.2-0.3-0.4), sec
t on : (0.1-0.2-0.3-0.4), sec
Instantaneous pick-up Ii
(2-3-4-6-8-10-12-15-off)× In
Ground-fault pick-up Ig
(0.2-0.3-0.4-0.5-0.6-0.7-0.8-1-off)× In
Ground-fault tripping delay tg t off : (0.05-0.1-0.2-0.3-0.4)
t on : (0.1-0.2-0.3-0.4)