1. Keep pushing the OFF button when the circuit breaker in a trip condition,
and insert a handle to the body of the circuit breaker.
2. Check the draw-out handle properly inserted and then push the lock
plate and turn the draw-out handle counterclockwise in order to insert
the breaker.
3. When the breaker reaches the TEST position, the lock plate automatically
projects and the draw-out handle is locked.
4. Push in the lock plate and turn the draw-out handle again
counterclockwise until the lock plate projects, At this time, the draw-out
operation is finished with indicator which shows DISCONNECTED
position.
Caution
1. Please stop handle operation when draw in/out locking device protrudes.
2. Draw in or out by moving handle right or left side when draw in/out locking device can not be
inserted.
Draw-out operation procedure
4. Draw-out operation
5. The circuit breaker indicated with ‘DISCONNECTED’ can be separated safely from the cradle by
removing a draw in/out handle and releasing right and left locks.
6. Use a lifting hook to separate a circuit breaker from a cradle.