Chapter 5 - Parameter List
63
Keypad Display Setting Range
Code Description
LCD 7-Segment
LCD 7-Segment
Units
Factory
Default
Adj.
During
Run
Page
None 0
Int. DB-R 1
FU2-75
DB (Dynamic Braking)
Resistor Mode Selection
DB mode 75
Ext. DB-R 2
- Int. DB-R
Yes
115
FU2-76
24
Duty of Dynamic Braking
Resistor
DB %ED 76 0 to 30 [%] 1 10 [%] Yes
115
FU2-79
Software Version S/W version 79 Ver x.xx - - - 116
FU2-81
25
2
nd
Acceleration Time 2nd Acc time 81 0 to 6000 [sec] 0.1
5.0 [sec]
Yes
FU2-82
2
nd
Deceleration Time 2nd Dec time 82 0 to 6000 [sec] 0.1
10.0 [sec]
Yes
FU2-83
2
nd
Base Frequency 2nd BaseFreq
83 30 to FU1-20 0.01
60.00 [Hz]
No
Linear 0
Square 1
FU2-84
2
nd
V/F Pattern 2nd V/F 84
User V/F 2
- Linear No
FU2-85
2
nd
Forward Torque Boost
2nd F-boost 85 0 to 15 [%] 0.1
2.0 [%] No
FU2-86
2
nd
Reverse Torque
Boost
2nd R-boost 86 0 to 15 [%] 0.1
2.0 [%] No
FU2-87
2
nd
Stall Prevention Level
2nd Stall 87 30 to 150 [%] 1 150[%] No
FU2-88
2
nd
Electronic Thermal
Level for 1 minute
2nd ETH 1min
88 FU2-89 to 200 [%] 1 150 [%]
Yes
FU2-89
2
nd
Electronic Thermal
Level for continuous
2nd ETH cont
89
50 to FU2-88
(Maximum 150%)
1 100 [%]
Yes
FU2-90
2
nd
Rated Motor Current
2nd R-Curr 90 1 to 200 [A] 0.1
3.6 [A] No
116
No 0
FU2-91
Read Parameters into
Keypad from Inverter
Para. Read 91
Yes 1
- No No
No 0
FU2-92
Write Parameters to
Inverter from Keypad
Para. Write 92
Yes 1
- No No
116
No 0
All Groups 1
DRV 2
FU1 3
FU2 4
I/O 5
FU2-93
Initialize Parameters Para. Init 93
EXT 6
- No No 117
FU2-94
Parameter Write
Protection
Para. Lock 94 0 to 255 1 0 Yes
117
FU2-99
Return Code Not displayed 99 Not available
[PROG/ENT]
or
[SHIFT/ESC]
- 1 Yes
117
Note: FU2-41, 42, 43, 44, 45, 46 not displayed when FU2-39 is set to V/f or Slip compen.
24
Code FU2-76 appears only when FU2-75 is set to ‘Ext. DB-R’.
25
Code FU2-81 through FU2-90 appear only when one of I/O-12 ~ I/O-14 is set to ‘2nd function’.