11-2
z Hardware specification
Item Specification
Installation Use S+, S- terminals on control terminal block
Power supply Use Insulated power from the inverter power supply
z Communication specification
Item Specification
Communication
speed
19,200/9,600/4,800/2,400/1,200 bps selectable
Control procedure Asynchronous communication system
Communication
system
Half duplex system
Character system ASCII (8 bit)
Stop bit length Modbus-RTU: 2 bit LS Bus: 1 bit
Sum check 2 byte
Parity check None
11.3 Installation
z Connecting the communication line
Connect the RS-485 communication line to the inverter’s (S+), (S-) terminals of the control
terminals.
Check the connection and turn ON the inverter.
If the communication line is connected correctly set the communication-related parameters as the
following:
DRV-03 [Drive mode]: 3(RS485)
DRV-04 [Freq. mode]: 7(RS485)
I/O-60 [Inv. Number]: 1~250 (If more than 1 inverters are connected, be sure to use different
numbers for each inverter)
I/O-61 [Baud-rate]: 3 (9,600 bps as Factory default)
I/O-62 [Lost Mode]: 0 - No action (Factory default)
I/O-63 [Time-Out]: 1.0 sec (Factory default)
I/O-59 [Comm. Prot]: 0 - Modbus-RTU, 1 – LS BUS