Operating Manual V25/09.2019   
Ventus / Ventus-X / V200A
 
  Chapter 10 Connections  19 
(for SDI12 connection please always follow the detailed notes in Chap. 10.7) 
 
The connection cable screen must NOT be laid to ground in the control panel for 
 Ventus 
! 
The 
Ventus
 will be earthed through the screws with the earthed mast . 
 
 
The connection cable screen MUST be laid to ground in the control panel for V200A ! 
 
If the equipment is not connected correctly 
-  It may not function 
-  It may be permanently damaged 
-  The possibility of an electrical shock may exist under certain circumstances 
10.1  Supply Voltage 
The supply voltage for 
Ventus
 is 24V DC ± 10%. The power supply unit used must be approved 
for operation with equipment of protection class III (SELV). 
10.2  RS485 Interface 
The equipment has an electrically isolated RS485 interface for configuration, measurement 
polling and the firmware update. 
The RS485 interface is designed as optionally half or full duplex, 2 or 4 wire connection.  
The following operating restrictions exist depending on the half or full duplex operation setting: 
Autonomous telegram transmission is 
possible 
No autonomous telegram transmission 
possible 
Transmission of values via current output is 
not possible 
Transmission of values via current output is 
possible 
Heating control via control pin is possible 
Heating control via control pin is possible 
Triggering of NMEA telegram transmission 
over Control-PIN is possible 
Triggering of NMEA telegram transmission 
over Control-PIN is not possible 
Firmware update not possible 
Restrictions in full and half duplex operation 
 
See page 32 for technical details. 
10.3  Analog Interface Circuits 
2 analog interface circuits are provided for analog data transmission. Both are updated every 
250ms. 
Interface A can be configured for 0 or 4-20mA current output, 0 or 2-10V voltage output as well 
as for frequency output in the range from 2 – 2000Hz (with adjustable voltage level up to 10V) 
Note: For the use of the analog outputs the serial communication protocol must be set to UMB 
binary! 
Interface B can be configured for 0 or 4-20mA current output and 0 or 2-10V voltage output 
The channels to be transmitted by way of these interfaces can be adjusted with the aid of the 
UMB-Config-Tool. The default values are Channels 400 (current wind speed in m/s (A)) and 500 
(current wind direction (B)). 
The scaling of the outputs is also adjustable. 
The maximum load on the current output is 300 . 
 
   
  
1
 Factory setting