EasyManua.ls Logo

Lumel N31U - Page 18

Lumel N31U
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
N31U User manual
Parameter symbol Description Range of changes
Enable or disable the
individual characteristics.
The OFF setting makes
possible to disable the
individual characteri-
stic function.
Default: OFF
OFF – individual characteristic disabled.
ON – individual characteristic enabled.
Number of points of the
individual characteristic.
Default: 2
2...32
The rst point of the indi-
vidual characteristic - the
value measured directly
or the value converted
by the mathematical fun-
ction.
Default: 0
-99999...999999
Number of the item for
moving window method
averaging. Each item is
a measurement taken in
SAVG time.
Default: 1
1...3600
Selection of resistance
compensation method
of the connection cables
during resistance or tem-
perature measurements
using RTD sensors or
terminals temperature
compensation for tempe-
rature measurement with
thermocouple sensors.
Default: AUTO
AUTO – automatic compensation of the terminals temperature is ena-
bled (for measurements using the thermocouples) or cables resistance
compensation for resistance measurements (a 3-wire system is required).
MANUAL – manual compensation of the measuring value. The tempe-
rature value of the terminals is determined by MCOMP setting for mea-
surements using the thermocouples. The resistance value of connecting
cables is determined by MCOMP setting for resistance measurements.
The resistance of the
connecting cables or
terminals temperature
during manual compen-
sation (MANUAL).
Default: 0
-30...70 – for the input set to measure using the thermocouples.
0...20 – for resistance measurement or temperature measurement using
the RTD sensors.
Mathematical function
selection which should be
applied for the measuring
value. The mathematical
function is applied before
the value is converted by
the individual charac-
teristic.
Default: NONE
NONE – no additional mathematical operations.
Sqr – measuring value is squared.
Sqrt – square root of the measuring value.
Inv – reciprocal of the measuring value.
InvSq – reciprocal of the measuring value is squared.
InvSt – square root of reciprocal of the measuring value.

Related product manuals