23
Internal
6. Specifications
CAPACITY* 6000 VA / 4800 W
INPUT
Voltage Range
Low Line Loss
110 VAC ± 3 % at 50% Load;
176 VAC ± 3 % at 100% Load
Low Line Comeback Low Line Loss
V
olta
g
e + 10V
Hi
g
h Line Loss 280
V
AC ± 3 %
Hi
g
h Line Comeback Hi
g
h Line Loss
V
olta
g
e - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz s
y
stem
(
Default settin
g)
56Hz ~ 64 Hz @ 60Hz system
Phase Sin
g
le
p
hase with
g
round
Power Factor
0.99 at 100% Load
OVCD Im
p
lemented, Cut-off when in
p
ut volta
g
e 100
V
ac and 280Vac
OUTPUT
Output voltage 208/220/230/240VAC (selectable)
AC Voltage Regulation ± 1%
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Fre
q
uenc
y
Ran
g
e
(
Batt. Mode
)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 H
z
Overload
A
C mode 105%~110%: 30min; 110%~130%: 5min; >130% : 10sec
Battery mode 105%~110%: 3min; 110%~130%: 30sec; >130% : 10sec
Current Crest Ratio 3:1 max
Harmonic Distortion
3.5 % THD (Linear Load)
5 % THD (Non-linear Load)
Transfer Time
Line Battery 0 ms
Inverter Bypass 0 ms
EFFICIENCY
A
C mode > 92%
Batter
y
Mode > 90%
BATTERY
Batter
y
Typ
e Sealed Maintenance Free Batteries
Numbers 16
Charging Current
Default: 4
A
± 10%
Max.: 1A, 2A, 4A, 6A (Adjustable)
Char
g
in
g
Volta
g
e 218.4V ± 1%
PHYSICAL
Dimension, DXWXH
(
mm
)
369 x 190 x 318
Net Weight (kgs)
12.5
±
5
%
Gross Weight (kgs)
14.5
±
5
%
ENVIRONMENT
O
p
eration
T
em
p
erature 0 ~ 40°C
O
p
eration Humidit
y
<95 % and non-condensin
g
O
p
eration Altitude** <1000m
A
coustic Noise Level Less than 55dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Su
pp
orts Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and
MAC
SNMP Card
(
O
p
tion
)
Power mana
g
ement from SNMP mana
g
er and web browser
* Derated capacity to 60% of max capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per
100m.
***Product specifications are subject to change without further notice.