CDA3000 Operation Manual
5-3
5 Diagnosis/Fault rectification
1
2
3
4
5
A
DE
EN
FR
IT
ES
FR
5.4 User errors in
K
EYPAD
operation
5.5 User errors in
S
MARTCARD
operation
5.6 Errors in power
switching
Error Cause Remedy
ATT1 Parameter cannot be changed at current
user level or is not editable
Select user level 1-MODE higher.
ATT2 Motor must not be controlled via the CTRL
menu.
Cancel start signal from a
different control location.
ATT3 Motor must not be controlled via the CTRL
menu because of error state.
Reset error.
ATT4 New parameter value impermissible Change value.
ATT5 New parameter value too high Reduce value.
ATT6 New parameter value too low Increase value.
ATT7 Card must not be read in current state. Reset start signal.
ERROR Invalid password Enter correct password.
Table 5.2 KEYPAD user error: Reset with Start/Enter
Error Meaning Remedy
ERR91 S
MARTCARD write-protected
Use different
S
MARTCARD
ERR92 Error in plausibility check
ERR93 S
MARTCARD not readable, wrong inverter type
ERR94 S
MARTCARD not readable, parameter not compatible
ERR96 Connection to S
MARTCARD broken
ERR97 S
MARTCARD DATA invalid (checksum)
ERR98 Insufficient memory on S
MARTCARD
ERR99 Selected area not present on SMARTCARD, no parameters
transferred to S
MARTCARD
Table 5.3 SMARTCARD ERROR: Reset with Stop/Return
Error Cause Remedy
Power on. Inverter module
shows no response (LEDs
off).
If switching is too frequent,
the device protects itself by
means of high-resistance
isolation from the system.
After a rest phase of a few
minutes the device is ready
to start once again.