A.4 Project planning
notes for multi-
motor operation
Topic Project planning notes
Current configura-
tion of inverter
module
The sum of the motor currents must be less than the rated output current
of the inverter module
Σ of motor currents, (I
M1
+ I
M2
+ I
Mn
) < Iinverter
Motor control
method
Multi-motor operation is only permitted with the VFC motor control
method.
Motor chokes A motor output choke must always be used. The motor choke limits the
du/dt and thus the leakage currents, and protects again switching volt-
age overload resulting from switching of the motor inductance.
Motor cable length The total length of the overall motor cable is produced by adding the
individual lengths per motor.
Motor protection In multi-motor operation the parallel-connected motors cannot be
protected by the inverter module. As a result, depending on application
the motor protection should be provided by means of external motor
circuit-breakers or thermistor protective relays.
All motors have
the same power
output
In this application the torque characteristics of all motors remain roughly
equal.
The motors have
different power
outputs
If the motor outputs are very different, problems may occur on startup
and at low speeds. This is because of the high stator resistance of small
motors and the resultant high voltage drop on the stator coil.
In practice: With a power ratio of around 1:4 between the motors, the
starting torque of the smallest motor is still approx. 70%
of the nominal torque. If the torque of approx. 70% is not
sufficient, a larger motor must be used.
If all the motors are started together, the small motor will
start up later, because the slip frequency is higher.