CDD3000-HF Operation Manual
4-3
4  Commissioning
DE
EN
FR
IT
ES
FR
1
2
3
4
5
A
 
Note: For more information refer to the DRIVEMANAGER Manual.
Step Action Comments
1
Connect your PC to the CDD3000-HF 
of the first drive and switch on the 
power to the CDD3000-HF.
Use a standard serial cable (9-pin 
D-SUB, pin-and-socket) e.g. LUST 
accessory CCD-SUB90x .
2
START DriveManager.
Automatically connects to the linked 
CDD3000-HF.
If the connection fails, check the bus settings in the Communication > Bus 
Configuration menu and try again by clicking on the icon.   
3
Save the current settings by clicking 
on the icon  ,
either in  the parameter database 
(directory: c:/../userdata) of the 
D
RIVEMANAGER or to a floppy disk (a:/).
Clicking on the icon always saves the 
current settings of the connected 
device. Assign the file a name of your 
choice.
If you are using the “Positioning, fully 
programming” preset, also save the 
positioning programs and data.
1)
4
Disconnect with 
5
Connect your PC to the CDD3000-HF of the next drive and switch on the 
power to the CDD3000-HF.
6
Click on the icon to make a connection between the DRIVEMANAGER 
and the newly connected device. 
7
Choose the icon   to load 
the data set saved in step 3 into the 
device (select all files).
The data set is stored in the device.
The selection box shows all the stored 
files in the data set.
8
Save the setting by clicking on the “Save setting in device” button.
Repeat steps 5 ... 8 on each additional CDD3000-HF.
1) For details of save operation see  Section 4.3.9.
Remember to save the 
setting.
Saving a data set from the 
device to a file
Load data set from file into 
device