CDD3000-HF Operation Manual
2-3
2  Mechanical installation
DE
EN
FR
IT
ES
FR
1
2
3
4
5
A
2.3 Wall mounting
 
 
Figure 2.1 Mounting clearances (see Table 2.1)  
Step Action Comment
1
Mark out the position of the tapped holes 
on the backing plate. 
Cut a tap for each fixing screw in the 
backing plate. 
Dimensional drawings/hole 
spacing see Table 2.1.
The tapping area will provide 
you with good, full-area contact.
2
Mount the drive controller for highspeed 
drives vertically on the backing plate.
Pay attention to the mounting 
clearances!
The contact surface must be 
metallically bright.
3
Mount the other components, such as the 
mains filter, line choke etc., on the 
backing plate.
Mains filter max. 20 cm below 
the drive controller for 
highspeed drives
4
Continue with electrical installation in 
section 3.
Note the following points:
• Air must be able to flow unhindered through the device. 
• The backing plate must be well grounded.
• The best result for effective EMC installation is attained with a 
chromated or galvanized backing plate. If backing plates are 
varnished, the coating must be removed in the area of the contact 
surface!
E
E1
G
F
CM-xxxx
F
UM-xxxx
38.5
60
30
60
With ventilator grille