3-12
CDD3000-HF Operation Manual
3  Installation
Hall-IC encoder
With the CDD3000-HF motor integrated Hall-IC-switches can also be
evaluated. These can be electrically aligned to 90° or 120°.
Cable type For the evaluation of these Hall-IC’s you require a cable with integrated
adaptation of the Hall-IC-signals to the high frequency drive CDD3000-
HF.
Connector The two Hall-IC's must be connected via terminal X7 on the CDD3000-
HF.
Figure 3.6 Hall-IC cable KHI-xxx
Minimum bending radius:
  in fixed installation
  in flexible use
90 mm
40 mm
100 mm
90 mm
Temperature range:
  in fixed installation
  in flexible use
-40 ... +85 °C -35 ... +80 °C
-35 ... +80 °C
-40 ... +85 °C
Cable diameter approx. 8.8 mm 8.0 mm 8.8 mm
Material of outer sheath PUR PUR PUR
Resistance
Resistant to oil, 
hydrolysis and microbic 
attack  (VDE0472),
UL 20233 
80 °C - 300 V
Resistant to oil, hydrolysis and microbic 
attack  (VDE0472)
Resistant to oil, 
hydrolysis and 
microbic attack  
(VDE0472),
UL 20233 
80 °C - 300 V
1) xxx = Length of cable in metres, standard lengths: xxx = 05, 10 m; maximum 50 m (longer lengths on request)
KRY-KSxxx
1)
KGN-KSxxx
1)
KGS-KSxxx
1)
KGH-KSxxx
1)
Table 3.6 Technical data of LUST encoder cables