CDD3000-HF Operation Manual
A-3
DE
EN
FR
IT
ES
FR
1
2
3
4
5
A
CDD34.008-HF to CDD34.032-HF
1)
Data referred to output voltage 400 V and switching frequency 8 kHz
.
Designation
Technical data
CDD34.008-HF
CDD34.010-HF
CDD34.014-HF
CDD34.017-HF
CDD34.024-HF
CDD34.032-HF
Output, motor end
1)
Device rated power 5.4 kVA 6.9 kVA 9.7 kVA 11.8 kVA 16.6 kVA 22.2 kVA
Voltage 3 x 0 ... 400/460 V
Continuous current (RMS) (I
N
)
7.8 A 10 A 14 A 17 A 24 A 32 A
Peak current 1.8 x I
N
for 30 s
14 A 18 A 25 A 31 A 43 A 58 A
Rotating field frequency 0 ... 1600 Hz
Switching frequency of power stage 4, 8, 12, 16 kHz
Input, mains side
Mains voltage 3 x 400 V / 3 x 460 V -25 % +10 %
Current (with line choke) 8.2 A 10.5 A 14.7 A 17.9 A 25.3 A 33.7 A
Frequency 50/60 Hz ±10 %
Power loss at 4 / 8.16 kHz [W] 150 / 177 187 / 222 225 / 283 270 / 340 330 / 415 415 / 525
Braking chopper power electronics
Peak braking power with int.
braking resistor (only with version
CDD34 ..., Wx.x, BR)
6.0 kW
at 90
6.0 kW
at 90
6.0 kW
at 90
Minimum ohmic resistance of an
externally installed braking resistor
81
47 22