CDD3000-HF Operation Manual
3-13
3  Installation
DE
EN
FR
IT
ES
FR
1
2
3
4
5
A
3.4 Mains 
connection
 
 
Wire 
colour
Function
red +Ub
yollow Hall A
green Hall B
black ground
Table 3.7 pin assignment KHI-xxx
Step Action Comment
1
Define the wire cross-section 
dependent on the maximum current and 
ambient temperature.
Wire cross-section to VDE0100, 
part 523
2
Wire the CDD3000-HF drive controller 
with the mains filter, max. line length 
0.3 m (with unshielded cable)! 
Step not applicable for BG1 to 
BG4; up to 11.8 kVA the mains 
filter is built-in.
3
Wire the line choke
1)
.
Reduces the voltage distortions 
(THD) in the system and extends 
the service life.
4
Install a circuit-breaker K1 (power 
switch, contactor, etc.).
Do not connect the power!
5
Use mains fuses (type gL) or miniature 
circuit-breakers (trip characteristic C) to 
cut the mains power to all poles of the 
CDD3000-HF drive controller. 
To protect the cable in 
accordance with VDE guidelines
1)
 See appendix A.4.
Connection  of the CDD3000-HF drive controller via a line choke with a short circuit 
voltage of 4 % of the mains voltage (u
k
 = 4 %) is obligatory:
1.
Where the CDD3000-HF drive controller is used in applications with interference 
corresponding to environment class 3, as per EN 61000-2-4 and above (hostile 
industrial environment).
3.
Where there is a requirement to comply with the limit values for variable-speed 
electric drives (see standard EN 61800-3/ IEC 1800-3)
4.
Where there is a dc link between multiple CDD3000-HF drive controller.