Page #1 background image
Lutron | 1
EcoSystem to 0 10 V- Interface | Install Guide
Customer Assistance: +1.844.LUTRON1
EcoSystem Link
EcoSystem
to 0 –10 V-
Interface
EcoSystem
Ballast
EcoSystem Ballast EcoSystem
LED Driver
Keypad
Lighting Remote
IR Receiver
0 –10 V- Driver
EcoSystem Master*
(GRAFIK Eye QS,
Quantum hub, etc.)
ATTENTION: Please read this guide before installing.
TVI-LMF-2A
120 277 V~ 50/60 Hz 2 A
EcoSystem: 18 V- 250 mA
0 10: 10 V- 25 mA
Overview
The EcoSystem to 0 –10 V- Interface provides a control
gateway from an EcoSystem link to a 0 –10 V- compatible
lighting device, typically an LED driver.
It allows for individual addressability of the 0 –10 V- device,
but only provides one-way communication from the controls
to the 0 –10 V- device. This interface is for single-fixture
control only. For fixtures that have multiple drivers installed
(such as two or three drivers being needed to reach certain
output wattages), only one interface may be necessary. This
interface is not intended for control of multiple fixtures.
System Example
*Does not count as one of the 64 devices allowed on the EcoSystem link
Specifications
Power
Maximum interface power consumption (at any voltage):
< = 1.0 W when output load is turned on
< = 0.5 W when output load turned off (“standby”)
• Relay Output:
2 A of electronic load, 5 drivers maximum
Input power must be unswitched
0–10 V- Control
Current rating: 25 mA max (sink only)
Maximum 0 10 V- wire length: 10 ft (3 m) from
interface to driver
Class 1 or Class 2 wiring allowed, isolated from line and
EcoSystem link
• Voltage Range:
Off: < = 0.5 V-
Minimum light level: 1 V-
Maximum light level: 10 V-
Compliant to IEC 60929 Annex E2 standard
(“Control by DC voltage”)
Note:
It is possible to connect more than 1 driver within a fixture
to an interface, with a maximum of 5 drivers. The interface
controls up to 2 A of connected load. If more than one
driver is attached, the drivers are controlled as a single
zone—individual control of multiple attached drivers is not
possible.
TVI-LMF-2A
English

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lutron Electronics EcoSystem and is the answer not in the manual?

Lutron Electronics EcoSystem Specifications

General IconGeneral
BrandLutron Electronics
ModelEcoSystem
CategoryRecording Equipment
LanguageEnglish

Related product manuals