User Guide HC - Copyright © 2008 MAC3. All right reserved.
Disegno 6328
37
Via Baldanzese, 149 50041 Calenzano FI
Tel. 055 8877672 – Fax 8877068
www.mac3.it - e-mail: mac3@mac3.it
Maintenance Menu Parameters Hydrocontroller
Name Range description
Lanuguage [Italiano,English] Language desired
Pressure Shock [0, 1] It is set to 1 wh
en it measured a pressure more than double of
the system pressure
SlowRestartNumb. [0, 100] Number of the slow restart for the autoclave, restart after dry
running protection (1 each 50 minutes)
Max.Motor current [0.45, 10.000] Max value rms for phase current
Leakages [0, 100] Number of big leakages
Tot. ShortC. Done [0, 1000] Counter for short circuits phase-phase and phase-ground.
Default value 40.
RemoteON Enable [ON,OFF] If ON, the inverter is in STANDBY and wait external command
to start
Sector1 Pressure [1, 7.5] Available on in GardenMode = ON
Sector2 Pressure [1, 7.5] Available on in GardenMode = ON
Sector3 Pressure [1, 7.5] Available on in GardenMode = ON
Sector4 Pressure [1, 7.5] Available on in GardenMode = ON
System Pressure [1, 7.5] Desired Pressure for the System
NoGardenRestPres [1, 7.5] Restart pressure of the Hydrocontroller, it works only in
GardenMode = OFF
Rotation Sense [0, 1] It changes the rotation sense of electropump via software
(only with three-phase electro pumps)
Software Release It displays the model of Hydrocontroller and the software
version installed in the device.
ResetFactorsConf [0, 1] Set = 1 set all parameters in factory configuration
System Start [ON,OFF] Powers or Not the electropump
Save & Exit with ENTER ENTER key: saved in permanent memory all’ the parameters
To exiting this menu, during the usual visualization of the parameters, you need to arrive at
the last parameter till the display:
Press the key ENTER and exit the menu; all the parameters are saved in permanent
memory.
Save&Exit