What to do if my MacroAir Technologies Diamond HVLS shows an overcurrent problem?
- KKelly BrownAug 1, 2025
If your MacroAir Technologies Fan is showing an overcurrent error, it could be due to several reasons: * A short circuit or grounding problem in the motor cables. Inspect the motor cables and remove any short circuits. * The load being too heavy. Measure the current flowing into the motor. If it exceeds the drive's rated current, consider replacing it with a larger capacity unit. Also, check for sudden fluctuations in the current level and reduce the load to avoid these changes, or switch to a larger drive. * The motor cable being too long. In this case, using a larger drive may resolve the issue.