How to resolve Hall Error on MacroAir Technologies EnergyLogic AVD3?
- KKatherine JonesSep 23, 2025
To resolve a Hall Error with your MacroAir Technologies Fan, confirm that the hall sensor is properly plugged into the drive.
How to resolve Hall Error on MacroAir Technologies EnergyLogic AVD3?
To resolve a Hall Error with your MacroAir Technologies Fan, confirm that the hall sensor is properly plugged into the drive.
What to do if there is a Supply Voltage Low Fault in MacroAir Technologies Fan?
If you are experiencing a Supply Voltage Low Fault with your MacroAir Technologies Fan, where the controller disables the fan because the bus voltage is below the threshold, here are some steps to take: First, turn the incoming power off for two minutes, then turn it back on. Next, confirm that the incoming power is within the fan's specifications. Consider whether there have been any recent power outages or storms in the area. Lastly, ensure that the motor wiring is correct.
What to do if MacroAir Technologies EnergyLogic AVD3 shows Supply Voltage High Warning?
If you're getting a Supply Voltage High Warning on your MacroAir Technologies Fan because the controller detects the bus voltage is above the threshold, here's what you can do: Start by turning the incoming power off for two minutes, then turn it back on. Next, make sure the power supply is within the fan's specifications. Check for any power spikes using a power quality recorder. Finally, confirm that the motor wiring is correct.
What to do if MacroAir Technologies Fan shows Supply Voltage Low Warning?
If you're getting a Supply Voltage Low Warning on your MacroAir Technologies Fan because the controller detects the bus voltage is below the threshold, here's what you can do: First, turn the incoming power off for two minutes, then turn it back on. Next, confirm the incoming power is within the fan's specifications. Check if there have been any recent power outages or storms in the area. Finally, confirm that the motor wiring is correct.
How to fix COMM ERROR on MacroAir Technologies EnergyLogic AVD3?
To troubleshoot a COMM ERROR on your MacroAir Technologies Fan, consider the following steps: 1. Check if the touchpad was unplugged. 2. Ensure the CAT5 cable is under 100ft. 3. Verify the CAT5 cable is from the factory and hasn't been modified. 4. Confirm the CAT5 cable is shielded. 5. Make sure repeaters are properly installed on the network. 6. Double-check network splices. 7. Plug the touchpad directly into the board. 8. Test for 5VDC on the blue pair if the screen lights up, or test for 24VDC if the screen does not light up.
How do I fix EEPROM Read Write Error on MacroAir Technologies Fan?
To address an EEPROM Read Write Error with your MacroAir Technologies Fan, turn the incoming power off for two minutes, then turn it back on.
What to do for Ambient Temperature High Warning in MacroAir Technologies EnergyLogic AVD3?
To address an Ambient Temperature High Warning in your MacroAir Technologies Fan: 1. Confirm that the ambient temperature is below 50C. 2. Start the fan earlier in the day before the ambient temperature rises.
What causes a Stalled Rotor in MacroAir Technologies Fan?
If your MacroAir Technologies Fan has a Stalled Rotor, take these steps: 1. Ensure that there are no obstacles in the way of the blades. 2. Ensure that blades turn freely by hand.
What does Heatsink Temperature High Warning mean for MacroAir Technologies EnergyLogic AVD3?
If your MacroAir Technologies Fan displays a Heatsink Temperature High Warning, the controller is reducing the torque command because the heatsink has reached 75C. The fan will return to full speed when the temperature falls below this value. To resolve this: 1. Confirm that the heatsink temperature is below 90C. 2. Ensure that the end caps are open and there is no blockage in the blades (AVD3). 3. Confirm that the quick link on the safety cable is not pulling the rubber boot closed (AVD3). 4. Confirm that the ambient temperature is below 50C. 5. Start the fan earlier in the day before the ambient temperature rises.
What should I do for Heatsink Temperature High Fault in MacroAir Technologies EnergyLogic AVD3 Fan?
To resolve a Heatsink Temperature High Fault in your MacroAir Technologies Fan: 1. Check that the heatsink temperature is below 110C. 2. Ensure the end caps are open and there are no blockages in the blades (AVD3). 3. Confirm the quick link on the safety cable isn't pulling the rubber boot closed (AVD3). 4. Verify the ambient temperature is below 50C. 5. Start the fan earlier in the day before the ambient temperature rises.
| Model | EnergyLogic AVD3 |
|---|---|
| Manufacturer | MacroAir Technologies |
| Power | 1.5 HP |
| Motor Type | Direct drive |
| Voltage | 120/240V |
| Application | Commercial, Industrial |
| Speed Settings | Variable Speed |
Details key safety features and installation requirements for fans.
Discusses structural support requirements and maximum hanging weight for fans.
Specifies the maximum torque handled by the mounting system.
Advises checking relevant codes for compliance with regulations.
States fans should not be operated when wind is present.
Guidelines for fan placement near fire sprinklers and code compliance.
Advice on fan placement relative to lights, mezzanines, and HVAC outlets.
Lists the tools necessary for installation and maintenance of the fan.
Details required bolt kits for I-Beam, Glulam, and Unistrut mounting.
Installation steps for mounting to I-beams or steel trusses over 3 inches wide.
Installation steps for mounting to Glulams or wood beams.
Installation method for spanning components using Unistrut.
Instructions for installing the extension tube for the fixed angle mount.
Steps for attaching the motor unit to the mount and extension tube.
Procedures for installing the safety cable for fixed angle mounts.
Details required bolt kits for I-Beam, Glulam, and Unistrut mounting.
Installation steps for mounting to I-beams or steel trusses over 3 inches wide.
Installation steps for mounting to Glulams or wood beams.
Installation method for spanning components using Unistrut.
Instructions for installing the extension tube for the universal mount.
Steps for attaching the motor unit to the mount and extension tube.
Procedures for installing the safety cable for universal mounts.
Specific instructions for connecting low voltage single and three-phase power.
Specific instructions for connecting high voltage three-phase power.
Details how to connect the CAT5e cable to the drive's terminal block or RJ45 port.
Steps for installing the optional fuse disconnect switch for safety.
Schematic for connecting fans to an emergency stop system.
Schematic for remote on/off fan control via supervisory contacts.
Lists fault codes, their causes, symptoms, and troubleshooting tips.