© 2019 EnergyLogic, LLC Toll Free: 800 311 8828 Fax: 615 471 5202 www.energylogic.com i
Rev. Date 040819
Installation
Manual
AVD3
5901 Crossings Blvd
Antioch, TN 37013
www.energylogic.com
(800) 311-8828

Table of Contents

Questions and Answers

  • L
    Lisa GarciaSep 7, 2025
    How to troubleshoot Phase Current A High Fault on MacroAir Technologies EnergyLogic AVD3 Fan?
    • R
      Ryan BarnettSep 7, 2025
      To address a Phase Current A High Fault in your MacroAir Technologies Fan: 1. Turn the incoming power off for two minutes, then turn it back on. 2. Confirm that the power supply is within the fan’s specifications. 3. Confirm that the motor leads are stripped (gen 2 370).
  • H
    Heather HannaAug 22, 2025
    What to do if there is a Supply Voltage High Fault in MacroAir Technologies Fan?
    • C
      Cheryl WilliamsAug 22, 2025
      If you are experiencing a Supply Voltage High Fault with your MacroAir Technologies Fan, where the controller disables the fan because the bus voltage exceeds the threshold, try the following: First, turn the incoming power off for two minutes, then turn it back on. Next, confirm that the power supply is within the fan's specified range. Also, check for any power spikes using a power quality recorder. Finally, make sure that the motor wiring is correctly configured.
  • R
    Rachel CrossSep 5, 2025
    What does Motor Temperature High Warning mean for MacroAir Technologies EnergyLogic AVD3?
    • T
      Tyler RiggsSep 5, 2025
      If your MacroAir Technologies Fan shows a Motor Temperature High Warning, it means the controller is reducing the torque command because the motor has reached 100C. The fan will return to full speed when the temperature falls below this value. To address this: 1. Confirm that the motor temperature is below 90C. 2. Ensure that the end caps are open and there is no blockage in the blades (AVD3). 3. Confirm that the quick link on the safety cable is not pulling the rubber boot closed (AVD3). 4. Confirm that the ambient temperature is below 50C. 5. Start the fan earlier in the day before the ambient temperature rises.
  • J
    jstewartSep 3, 2025
    What should I do for Heatsink Temperature High Fault in MacroAir Technologies EnergyLogic AVD3 Fan?
    • D
      danielsnyderSep 3, 2025
      To resolve a Heatsink Temperature High Fault in your MacroAir Technologies Fan: 1. Check that the heatsink temperature is below 110C. 2. Ensure the end caps are open and there are no blockages in the blades (AVD3). 3. Confirm the quick link on the safety cable isn't pulling the rubber boot closed (AVD3). 4. Verify the ambient temperature is below 50C. 5. Start the fan earlier in the day before the ambient temperature rises.
  • T
    Thomas CrossSep 2, 2025
    What should I do for Motor Temperature High Fault in MacroAir Technologies EnergyLogic AVD3 Fan?
    • W
      William ClarkSep 2, 2025
      To resolve a Motor Temperature High Fault in your MacroAir Technologies Fan: 1. Check that the motor temperature is below 110C. 2. Ensure the end caps are open and there are no blockages in the blades (AVD3). 3. Confirm the quick link on the safety cable isn't pulling the rubber boot closed (AVD3). 4. Verify the ambient temperature is below 50C. 5. Start the fan earlier in the day before the ambient temperature rises.
  • A
    Aaron ThomasAug 31, 2025
    How to fix Receive Frame Error or Noise On Comm Lines on MacroAir Technologies Fan?
    • O
      Olivia MooreAug 31, 2025
      To address a Receive Frame Error or Noise on Comm Lines issue with your MacroAir Technologies Fan: 1. First, check if the touchpad was unplugged. 2. Ensure the CAT5 cable is under 100ft. 3. Verify the CAT5 cable is from the factory and hasn't been modified. 4. Confirm the CAT5 cable is shielded. 5. Make sure repeaters are properly installed on the network. 6. Double-check network splices. 7. Plug the touchpad directly into the board. 8. Confirm the firmware is 146 or above.
  • D
    Devin ThomasAug 30, 2025
    How to resolve Keep-Alive Timeout on MacroAir Technologies EnergyLogic AVD3?
    • J
      Jennifer JohnsonAug 30, 2025
      To troubleshoot a Keep-Alive Timeout with your MacroAir Technologies Fan: 1. First, check if the touchpad was unplugged. 2. Ensure the CAT5 cable is under 100ft. 3. Verify the CAT5 cable is from the factory and hasn't been modified. 4. Confirm the CAT5 cable is shielded. 5. Make sure repeaters are properly installed on the network. 6. Double-check network splices. 7. Plug the touchpad directly into the board.
  • A
    alicehallAug 29, 2025
    What to do if MacroAir Technologies Fan shows Fire Disconnect error?
    • R
      Regina MaldonadoAug 29, 2025
      To address a Fire Disconnect issue with your MacroAir Technologies Fan: 1. First, check if the touchpad was unplugged. 2. Note that a 1018 error is common if the touchpad is unplugged; pressing the reset button should clear the code and allow normal fan operation. 3. Confirm that the orange pair is twisted together inside the screen enclosure. 4. Ensure the orange pair runs throughout the entire CAT5 line. 5. Plug the touchpad directly into the fan to see if the fault clears.
  • L
    Leslie AdamsAug 27, 2025
    How to fix COMM ERROR on MacroAir Technologies EnergyLogic AVD3?
    • G
      gilbertdavidAug 27, 2025
      To troubleshoot a COMM ERROR on your MacroAir Technologies Fan, consider the following steps: 1. Check if the touchpad was unplugged. 2. Ensure the CAT5 cable is under 100ft. 3. Verify the CAT5 cable is from the factory and hasn't been modified. 4. Confirm the CAT5 cable is shielded. 5. Make sure repeaters are properly installed on the network. 6. Double-check network splices. 7. Plug the touchpad directly into the board. 8. Test for 5VDC on the blue pair if the screen lights up, or test for 24VDC if the screen does not light up.
  • V
    Vicki RoyAug 27, 2025
    What to do if MacroAir Technologies Fan shows Supply Voltage Low Warning?
    • M
      Mark FosterAug 27, 2025
      If you're getting a Supply Voltage Low Warning on your MacroAir Technologies Fan because the controller detects the bus voltage is below the threshold, here's what you can do: First, turn the incoming power off for two minutes, then turn it back on. Next, confirm the incoming power is within the fan's specifications. Check if there have been any recent power outages or storms in the area. Finally, confirm that the motor wiring is correct.

Summary

Caution & Safety

Key Safety System Components

Details key safety features and installation requirements for fans.

Weight Considerations

Discusses structural support requirements and maximum hanging weight for fans.

Torque

Specifies the maximum torque handled by the mounting system.

Check Federal, State, and Local Codes

Advises checking relevant codes for compliance with regulations.

Windy Conditions

States fans should not be operated when wind is present.

Fusing Chart

Fan Placement & Clearance

Sprinkler Systems and Fan Placement

Guidelines for fan placement near fire sprinklers and code compliance.

Other Information on Placement and Spacing

Advice on fan placement relative to lights, mezzanines, and HVAC outlets.

Fan Dimensions

Network Wiring (Optional)

Components (Fixed Angle Mount)

Components (Universal Mount)

Fan Components and Tools

Tools Required

Lists the tools necessary for installation and maintenance of the fan.

Fixed Angle Mount

Mounting Bolt Kits

Details required bolt kits for I-Beam, Glulam, and Unistrut mounting.

I-Beam (Steel Truss Mounting)

Installation steps for mounting to I-beams or steel trusses over 3 inches wide.

Glulam

Installation steps for mounting to Glulams or wood beams.

Unistrut

Installation method for spanning components using Unistrut.

Extension Tube

Instructions for installing the extension tube for the fixed angle mount.

Motor Unit

Steps for attaching the motor unit to the mount and extension tube.

Safety Cable Installation

Procedures for installing the safety cable for fixed angle mounts.

Universal Mount

Mounting Bolt Kits

Details required bolt kits for I-Beam, Glulam, and Unistrut mounting.

I-Beam (Steel Truss Mounting)

Installation steps for mounting to I-beams or steel trusses over 3 inches wide.

Glulam

Installation steps for mounting to Glulams or wood beams.

Unistrut

Installation method for spanning components using Unistrut.

Extension Tube

Instructions for installing the extension tube for the universal mount.

Motor Unit

Steps for attaching the motor unit to the mount and extension tube.

Safety Cable Installation

Procedures for installing the safety cable for universal mounts.

Guy Wire Installation

Drive Installation

Drive Installation (Low Voltage)

Specific instructions for connecting low voltage single and three-phase power.

Drive Installation (High Voltage)

Specific instructions for connecting high voltage three-phase power.

Control Wiring

Details how to connect the CAT5e cable to the drive's terminal block or RJ45 port.

Airfoil Installation

Disconnect Switch

Fuse Disconnect Switch Installation

Steps for installing the optional fuse disconnect switch for safety.

Emergency Disconnect Schematic

Schematic for connecting fans to an emergency stop system.

Enable (ON);Disable (OFF) Schematic

Schematic for remote on/off fan control via supervisory contacts.

Touchpad Remote Mounting

Touchpad Remote Navigation

Touchpad Remote Operation

Maintenance Information

Mounting Plate Dimensions

Mounting Bracket Dimensions

Touchpad Remote Dimensions

Troubleshooting

Fault Code Causes and Possible Solutions

Lists fault codes, their causes, symptoms, and troubleshooting tips.

Warranty and Technical Support

MacroAir Technologies EnergyLogic AVD3 Specifications

General IconGeneral
ModelEnergyLogic AVD3
ManufacturerMacroAir Technologies
Power1.5 HP
Motor TypeDirect drive
Voltage120/240V
ApplicationCommercial, Industrial
Speed SettingsVariable Speed