Macurco GD-xx Operation Manual
REV – 2.0.0 [34-2900-0027-6 ] 30 | Page
NOTE: GD-xx must be tested or calibrated at regular intervals in accordance with the requirements of the National
Fire Protection Association (NFPA) 720 or local code requirements. Macurco recommends testing and calibration at
a least once per year at a minimum but depending on the application and risk potential of the application a greater
frequency might be needed. Check with local authorities for any specific local regulations.
Contents of the Cal-Kit 1
• Cal-Kit 1 (30-0011-1110-2)
o Calibration Case
o Two feet of Tygon tubing
o Cal Hood-Macurco Pack
o 0.2 LPM Gas regulator (F)
Also needed are the following gas bottles depending on the target gas (Sold Separately):
• Hydrogen
o 70-0716-1758-6 Hydrogen H2 Cal Gas Cylinder 34L 10% LEL (M) (For Calibration and Testing)
o 70-0716-1759-4 Hydrogen H2 Cal Gas Cylinder 34L 20% LEL (M) (For Testing)
• Methane
o 70-0716-1754-5 Methane CH4 Cal Gas Cylinder 34L 10% LEL (M) (For Calibration and Testing)
o 70-0716-1755-2 Methane CH4 Cal Gas Cylinder 34L 20% LEL (M) (For Testing)
• Propane
o 70-0716-1756-0 Propane C3H8 Cal Gas Cylinder 34L 10% LEL (M) (For Calibration and Testing)
o 70-0716-1757-8 Propane C2H8 Cal Gas Cylinder 34L 20% LEL (M) (For Testing)
Cal-Kit 1 Information
Several detectors can be calibrated with one Cal-Kit. The only limitation is the amount of gas in the cylinder. The 34-
liter cylinder has approximately 170 minutes of continuous calibration run time. The gas cylinder should be replaced
when the pressure gauge on the regulator shows 25-psi or less.
Note: For optimum test results it is suggested that the unit be in clean air, green light on, and be in a low ambient air
flow.