36 Part Number 000014141 Rev 11 12/23
Installation Section 2
Design & Burst Pressure
Design Pressure 600 psig - 4137 kPa
Burst Pressure 2500 psig - 17237 kPa
Head Pressure Control Valve
Do not use a fan cycling control to try to
maintain discharge pressure. Compressor
failure will result. Any remote condenser
connected to a Manitowoc Ice Machine
must have the OEM head pressure control
valve installed. Manitowoc will not accept
substitute “off the shelf” head pressure
control valves.
Kits are available for head pressure control
installation:
• R404A Refrigerant - K00479
• R410A Refrigerant - K00221
Fan Motor
The condenser fan must be on during the
complete ice machine freeze cycle (do
not cycle on fan cycle control). The ice
maker has a condenser fan motor circuit
for use with a Manitowoc condenser. It is
recommended that this circuit be used to
control the condenser fan(s) on the multi-
circuit condenser to assure it is on at the
proper time. Do not exceed the rated amps
for the fan motor circuit listed on the ice
machine’s serial tag.
Internal Condenser Volume
The multi-circuit condenser internal
volume must not be less than or exceed
that used by Manitowoc. Do not exceed
internal volume and try to add charge to
compensate, as compressor failure will
result.
Model
Minimum
ft
3
(cm
3
)
Maximum
ft
3
(cm
3
)
IT0500N
IF0500N
0.020
(566)
0.030
(850)
IF0600N/IF0900N
IT0750N/IT0900N/
IT1200N
0.045
(1274)
0.060
(1699)
IT1500N/IT1900N
0.085
(2407)
0.105
(2973)
Heat of Rejection
Model Peak Average
IF0500N 6900 6100
IT0500N 6900 6100
IF0600N 13900 9000
IT0750N 13700 12800
IF0900N 16000 13000
IT0900N 16000 13000
IT1200N 24500 20700
IT1500N 27000 23000
IT1900N 30500 26100