Part Number STH039 8/13 45
Ice Thickness Check
After a harvest cycle, inspect the ice cubes in the ice
storage bin. The ice thickness probe is set to maintain
an ice bridge of 3 mm. If an adjustment is needed,
follow the steps below.
1. Turn the ice thickness probe adjustment screw
clockwise for a thicker ice bridge, or
counterclockwise for a thinner ice bridge.
Ice Thickness Adjustment
2. Make sure the ice thickness probe wire and
bracket does not restrict movement of the probe.
3 MM ICE BRIDGE
THICKNESS
ADJUSTING
SCREW
SV3114
SV3113