Safety Limit Checklist
The following checklists are designed to assist the
service technician in analysis. However, because
there are many possible external problems, do not
limit your diagnosis to only the items listed.
Safety Limit #1
Freeze time exceeds 60 minutes for 6 consecutive
freeze cycles.
Possible Cause Checklist
Improper installation
Refer to “Installation and Visual Inspection
Checklist” on page 52
Water System
Water Level set too high (water escaping through
over flow tube)
Low water pressure 1.37 bar minimum
High water pressure 5.52 bar maximum
High water temperature 32°C maximum
Clogged water distribution tube
Dirty/defective float valve
Defective water pump