TROUBLESHOOTING 2900 VALVE (CONTINUED)
General Service Hints For Meter Control
Problem: Softener Delivers Hard Water.
Cause could be that . . . Reserve Capacity Has Been Exceeded.
Correction: Check salt dosage requirements and reset program wheel to provide additional reserve.
Cause could be that . . . Meter Is Not Measuring Flow.
Correction: Check meter with meter checker.
7. Excessive Water In Brine Tank. A. Plugged Drain Line Flow Control.
B. Plugged Injector System.
C. Timer Not Cycling.
D. Foreign Material In Brine Valve.
E. Foreign Material In Brine Line Flow
Control.
A. Clean Flow Control.
B. Clean Injector and Screen.
C. Replace Timer.
D. Replace Brine Valve Seat And
Clean Valve.
E. Clean Brine Line Flow Control.
8. Softener Fails To Draw Brine. A. Drain Line Flow Control Is
Plugged.
B. Injector Is Plugged.
C. Injector Screen Plugged.
D. Line Pressure Is Too Low.
E. Internal Control Leak
F. Service Adapter Did Not Cycle.
A. Clean Drain Line Flow Control.
B. Clean Injector.
C. Clean Screen.
D. Increase Line Pressure To 20 P.S.I.
E. Change Seals, Spacers and Piston
Assembly.
F. Check Drive Motor And Switches.
9. Control Cycles Continuously. A. Misadjusted, Broken or Shorted
Switch.
A. Determine If Switch or Timer Is
Faulty and Replace It or Replace
Complete Power Head.
10. Drain Flows Continuously. A. Valve Is Not Programming Cor-
rectly.
B. Foreign Material In Control.
C. Internal Control Leak
A. Check Timer Program and Posi-
tioning of Control. Replace Power
Head Assembly If Not Positioning
Properly.
B. Remove Power Head Assembly
And Inspect Bore. Remove Foreign
Material and Check Control In Var-
ious Regeneration Positions.
C. Replace Seals and Piston
Assembly.
PROBLEM CAUSE CORRECTION