User Manual 34
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
* For FL1 to FL4:
To write these parameters:
0 for 10, 5 for 60,
1 for 20, 6 for 70,
2 for 30, 7 for 80,
3 for 40, 8 for 90,
4 for 50, 9 for 100
10.3.2 Addresses Of 1008S With Mass Flow
52
40052
Pulse Width
2(1)
R/W (00-50)
53
1
Low alarm Relay
Status
1
R, digital
54
2
High alarm Relay
Status
1
R, digital
55
3
Set point Relay
Status
1
R, digital
56
4
Pre warm Point
Relay Status
1
R, digital
57
5
Start/Pause batch
W(0 for Pause, 1 for Start)
58
6
To Clear Batch
Total
1
W, digital(1 for Clear)
59
7
To Clear
Integration Total
and Batch Total
1
W, digital(1 for Clear)
Sr. No.
Reg. No.
Parameter Name
Length in
bytes
(Words)
Read/Write
1
40001
High alarm
2(1)
R/W
2
40002
High alarm + 2
2(1)
R/W
3
40003
Low alarm
2(1)
R/W
4
40004
Low alarm + 2
2(1)
R/W
5
40005
Set point
2(1)
R/W
6
40006
Setpoint+2
2(1)
R/W
7
40007
Pre-warn
2(1)
R/W
8
40008
Prewarn+2
2(1)
R/W
9
40009
Conv-Factor
2(1)
R/W (00.00-99.99)
10
40010
Filter no
2(1)
R/W (1 to 25)
11
40011
Batch mode
2(1)
R/W (0 for Normal, 1 for Counter)
12
40012
Type of input
2(1)
R/W (0 for 0-5V, 1 for 1-5V,
2 for 0-20mA, 3 for 4-20mA,
4 for pulse)
13
40013
Type of Inst
2(1)
R/W (0 for indicator, 1 for Totaliser)
14
40014
Sqrt mode
2(1)
R/W (0 for Yes, 1 for No)
15
40015
Digital input
2(1)
R/W (0 for Yes, 1 for No)
16
40016
Digital filter
2(1)
R/W (0 for Yes, 1 for No)
17
40017
Time base
2(1)
R/W (0 for SECOND, 1 for MINUTE,
2 for HOUR, 3 for DAY)
18
40018
ZR+2
2(1)
R/W