EasyManuals Logo

Master Bilt Master Controller 2.0 User Manual

Master Bilt Master Controller 2.0
31 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
22
(1) Charge the system by weighing exact amount of refrigerant specified by Master-Bilt for the unit. Or,
(2) Charge 50% of the liquid receiver (if provided) rated holding capacity. Let the system run through the
pull down period until room temperature is closely reached, then gradually add refrigerant until actual
superheat “SUPH” on board is approaching superheat setpoint “SHSP”. Bubbles may be seen in the
sight glass.
(3) In a reverse cycle defrost system, there may not be a liquid receiver. Charge the system the working
amount of refrigerant calculated above. Let the system run through the pull down period until room
temperature is closely reached. Then gradually add refrigerant until actual superheat “SUPH” on board
is approaching superheat setpoint “SHSP”. Bubbles may be seen in the sight glass.
How to diagnose an overcharged system:
An overcharged system will not operate properly.
First, be sure that system is not leaking
Compressor may be short cycling
Frost building up on compressor suction section, suction filter or service valve
Low superheat alarm appears on the controller display constantly
Head pressure cut-out during defrsot for a reverse cycle defrost system
Solution:
Taking some refrigerant out of the system until on-board actual superheat “SUPH” is observed approaching
superheat setpoint “SHSP”.
Technical Notes
With the optional alarm relay the external temperature and alarm indicator should be connected to “C”
(common) and “NC” (normal close) terminals. The alarm does not indicate what causes the alarm. To
find out what has caused the alarm, check the onboard four-digit display for alarm codes and refer to
the diagnosis chart for corrective action. Thermostat wiring can be used for connection.
Defrost termination set point (DTSP) can be also set up to 80
o
F. When setting the defrost termination
temperature, make sure that the frost is free after each defrost. Also make adjustments to the
maximum defrost duration when necessary.
The superheat of each application can be set by the customer. Superheat 10-15
o
F is recommended
for winter operation, superheat 5-10
o
F for summer.
Always clear the “LOSH”, “HITA” and “LOTA” alarms after corrective action is taken. The sensor and
communication alarms cannot be cleared unless they are corrected.
Cat5/e communication cable should be rated 300 V 80
o
C or higher. If the wire is rated lower than 300
V, a separate conduit must be used for communication cables.
Follow the instructions in the Master-Bilt Condensing Unit and Refrigeration System Installation &
Operation Manual to perform the final check up before charging and starting up the system. Always
refer to this service manual, make sure all steps are understood. Don’t hesitate to call Master-Bilt
Customer Service Department at 800-684-8988 for technical assistance.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Master Bilt Master Controller 2.0 and is the answer not in the manual?

Master Bilt Master Controller 2.0 Specifications

General IconGeneral
BrandMaster Bilt
ModelMaster Controller 2.0
CategoryController
LanguageEnglish