TYPICAL SET POINTS FOR AMC CONTROLLER 2.0
Air/Electric Defrost Reverse Cycle Defrost
Low Temp High Temp Low Temp High Temp
SHSP 10 10 10 10
RMSP -10 35 -10 35
MXDT 35 35 20 20
DTSP 75 45 60 60
PMDN 3 3 3 3
DRAN 2 2 5 2
DFPD 0 0 0 0
HITA 25 50 25 50
HIDL 59 59 59 59
LOTA -20 20 -20 20
MOTM 2 2 2 2
MRTM 2 2 2 2
AIRD 5 3 5 3
MOP 55 80 55 80
MNPR 0 0 0 0
INTV 720 1440 720 1440
DFMD ELEC ELEC HGDF HGDF
REFR 404A 404A 404A 404A
ALSP 5 5 5 5