Mass Combi Pro 12/3000-150, 24/3500-100 ā User and Installation Manual
Float voltage (adjustable if User Defined).
8-16.00/16-32.00/32-64.00 V
Option to enable ground relay
Option to enable Energy save mode
The Combi starts scanning below this
inverted power level in Energy save
mode.
Select to base the input window upon
battery type default values or upon your
own preset values. Refer to section 4.2.4
Use battery type, user defined (Use
battery type: dynamic input window
still present, but not configurable)
High battery voltage for inverter switch off
(12/24/48V, user defined only).
13.00-16.00/26.00-32.00/52.00-
64.00V
High battery voltage for inverter switch to
DC High Off alarm (12/24/48V, user def.)
13.00-16.00/26.00-32.00/52.00-
64.00V
Low battery voltage at which the inverter
switches off when the battery current is
0-2% of nominal (12/24/48V, user def.)
9.50-13.00/19.00-26.00/38.00-
52.00V
Low battery voltage at which the inverter
switches off when the battery current is
2% of nominal (12/24/48V, user def.)
9.50-13.00/19.00-26.00/38.00-
52.00V
Low battery inverter switch off voltage,
batt. current 100% (12/24/48V, user def.)
9.50-13.00/19.00-26.00/38.00-
52.00V
Low battery inverter switch on voltage at
DC Low off alarm (12/24/48V, user def.)
10.00-13.00/20.00-26.00/40.00-
52.00V
Delay time before inverter switches off on
low battery voltage.
Define which AC input to be used under
which conditions, refer to section 4.3
Mains preferent, Gen preferent, Max
fuse prefer
Define under which conditions to use AC
output-2, refer to section 4.3
Events only, Generator input, Mains
input, Gen/Mains input, Always on
Mains fuse maximum value that can be
set in the monitoring tab
Power sharing mode option, chapter 3.
AC support mode option, chapter 3.
Generator AC input window
Generator AC input window
Generator AC input window
Generator AC input window
Time to trigger a Generator alarm
Time to trigger a Mains alarm