OPERATION
EN / Mass Sine 12/1200, 12/2000, 24/1500, 24/2500 & 48/2500 / June 2000
33
Remove the short circuit and reset the inverter by
switching it off and on.
“low battery”
The inverter is switched off if the battery voltage is
too low (see table below). If the voltage rises above
the values given below, the inverter restarts auto-
matically.
model 12V 24V 48V
switch off voltage 10V 19V 36V
switch on voltage 11V 22V 44V
“temperature”
The inverter switches off in high ambient temperatu-
res and /or sustained overload. After cooling down,
the inverter restarts automatically.
4.4 ON THE REMOTE CONTROL
If you use a remote control panel, put the on/off
switch to ‘remote’, and put the on/off switch on the re-
mote control panel to ‘on’.
The meaning of the illuminated LED’s is:
inverter on: inverter is switched on
failure: inverter is overloaded, overheated
or battery voltage is too low
If the failure lamp is lit you can check the nature of
the failure on the inverter front. See fig. 3 for a view
of the panel.