35
i-32V5
POWER FAILURE
•
•
•
UTILITIES BLOCK ALARM TABLE
Code DESCRIPTION Block
E00 Remote o Machine
E001 High pressure alarm Machine
E002 Low pressure alarm Machine
E005 Anfreeze alarm Machine
E006 Flow alarm Machine
E008 Compressor driver limitaon alarm Machine
E009 Discharge high temperature alarm Machine
E010 Solar collector high temperature alarm Solar pump
E018 Cooling high temperature alarm Machine
E020 Inverted trasductors pressure alarm Machine
E041 Inconsistent temperatures alarm Macchina
E050 DHW storage tank high temperature alarm Machine/sanitary
E101 Communicaon meout with Slave 1 Machine
E611 Water inlet probe failure Machine
E621 Water outlet probe failure Machine
E631 Compressor intake probe failure Machine
E641 Compressor discharge probe fault / high pressure switch trip Machine
E651 Outdoor air probe failure Machine
*E652 Mixer probe failure Machine
E661 DHW probe failure Machine
*E662 Solar storage tank probe failure Machine
E671 Plant remote probe failure Machine
*E672 Solar collector probe failure Machine
E691 Low pressure transducer failure Machine
E701 High pressure probe failure Machine
E711 0-10Vdc live input failure Machine
E801 Pressure inverter meout Compressor
E851 Inverter Hardware problem Compressor
E861 Motor current too high Compressor
E871 Heatsink over-heat protecon Compressor
E881 Supply voltage out of limits (DC Bus Error) Compressor
E891 Driving protecon-output phase loss Compressor
E901 Compressor driver and model mismatch Compressor
E911 Overload protecon Compressor
E921 PFC_POE over current Compressor
E931 Comunicaon error with main controller Compressor
E941 PFC converter fault Compressor
E951 Heatsink and/or ambient temperature sensor error Compressor
E961 Abnormal condion Compressor
E971 EEPROM not inialize Compressor
15. MODBUS VARIABLES
BAUD RATE 9600
PARITY EVEN
DATA BIT 8
STOP BIT 1
DEVICE ID 1