6
V-Rail
Physical Stop
Read and understand this entire manual before installation. Check with the local building department prior to installing this gate
operator to comply with local building code requirements. The gate must be installed in a location so that enough clearance is
supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment.
Concrete Pad
Operator Position on Concrete Pad
Operator in Front Position
Outside Property
Inside Property
Input Power
Positive Stop
Conduit Run
Operator MUST be level.
Concrete Pad
Check local building
codes in your area for
depth of concrete
before installation.
Install physical stops on BOTH
ends of rail to keep gate from
traveling off of rail.
Guide rollers MUST be Installed to keep gate upright.
6” above ground to avoid any flooding of the operator.
See page 7 for chain information.
24”
24”
Illustrations not to scale
Gate in Closed Position
4”
2” Gate Frame
10.5”
10.5”
6.2”
6.75”
7.5”7.5”
6.75”
Cover
1.5”
4”5”
6.5”
installation
The gate must be properly installed and work freely in both directions prior to installation of the gate operator.
operator in front mounting position (standard)
REQUIRED - AC input power wire.
Entrapment protection photocell . See page 14.
Entrapment protection sensing edge. See page 15.
In-ground loop wires. See page 16.
Conduit Guidelines and Suggestions
Concrete Depth Note: The heavier the gate, the deeper the concrete
pad should be. At least two feet recommended for heavier gate.
“Optional” Input Power Note:
24VDC low voltage power wires can be run
from a remote power supply (MAX Magic
Box) to power the gate operator if desired.
See page 11 for more information.
Secure gate operator to
concrete pad with four
(4) 1/2” x 3” (min)
sleeve anchors.
1/2
8.625”
12.75”
Conduit
Area
ONE Entrapment protection sensor MUST installed or
operator will NOT function. It MUST be MONITORED
and NORMALLY CLOSED (N.C.)