KK-641.002 Rev.No:1 01.08.12 ML-121X User Manual Page | 22
+Print by Category: The event logs are printed-out as being
categorized depending on the event types.
Fires: x
Evacuates: x
Faults: x
Pre-Alarms: x
+Print by List: All events are printed-out.
-Start to Print
-Clear Event Logs: All event logs are erased.
-Print Configuration: This feature is used to print-out panel settings.
+Edit Event: This feature allows determining for how the panel will give
warning in case of ‘New Device and ‘Disconnected Device’ states.
-Disconnected device: (Fault/Warning): The message is displayed in
case the panel cannot communicate with any device. In this case, the panel will give Fault or
Warning. It is possible to select the panel behavior upon disconnected device by this feature.
-New device: (Fault/Warning): The message displayed when detecting
a new device, which is not included in the configuration file. In this case, the panel will give
Fault or Warning. It is possible to select the panel behavior upon newly added device by this
feature.
+SLCU App. Software: Version update of panel loop cards can be done with
the aid of this feature. Version update can only be done by the manufacturer.
-LCU 1 B.V. (1.0.0) /A.P.P.V. (1.0.12)
+Contamination Control: The system devices may be contaminated in time
because of the environmental reasons. These devices can cause FALSE ALARMS. In order
to prevent this issue, a regular maintenance must be made periodically. Panel is able to
display contamination level of connected devices. Devices contamination levels can be
checked for one loop or for all loops.
+General:
+Automatic Control: In case this option is selected, devices
connected to the system are continuously checked for any contamination. Interrogation count
can be selected as (8, 16, 64, 255). The contamination control is done depending on the
selected value. An analogue value greater than 75 is considered as the contamination
threshold by the panel. Upon detecting any contaminated device, a message appears on the
screen. This message disappears after cleaning or replacing the device with the new one and
resetting the panel.
+Interrogation Count: x
-Measuring contamination status