Device-Specic Commands
9.0 Device-Specic Commands
The converter manages the following device-specic commands:
Command Details
128 Set/Reset Write Protect Mode
129 Clear All Device Status
130 Reset Totalizer
131 Read Tube Diameter
132 Read Coil Frequency
133 Read Low Flow Cut O
134 Read Density
135 Read Flow Direction
136 Read Mass Unit Enable
Command #128: Set/Reset Write Protect Mode
This command allows the user to enable or disable the write protection ag. The Command #128 takes eect only if
the write protect ag is enabled. The parameter that allows the change is set via display in the specic menu. Refer to
ProComm IOM Manual for the converter function code and MCP command.
Byte Format Description
Request Data Bytes 0 Enum Set / reset write protection
Response Data Bytes 0 Enum Write protect mode
Command-Specic
Response Codes
0 Success No command-specic errors
1 Undened
2 Error Invalid selection
3 - 4 Undened
5 Error Too few data bytes received
Command #129: Clear All Device Status
This command allows the user to clear all device status.
Byte Format Description
Request Data Bytes 0 Enum Set / reset write protection
Response Data Bytes 0 Enum Write protect mode
Command-Specic
Response Codes
0 Success No command-specic errors
1 Undened
2 Error Invalid selection
3 - 4 Undened
5 Error Too few data bytes received