82 AGR 055A through 100A IOMM AGR
cursor will advance to the Year position on the display. Use the Incr, Decr, and Enter keys to set the
correct Year.
Press the Next Item key. The display will show the current Day, Hour, Minute and Second. If this
information needs to be changed, follow the same procedure used to set the Date in the previous
section.
Menu #20: Daily Schedule—This section will help you to set the Daily Start/Stop time for
automatic operation of the chiller. Pressing the Next Menu key and the Next item key will advance
the display to the Daily Time Schedule. This is where the Start and Stop times for each day of the
week will be set using the 24 hour format. Beginning with Sunday, use the Incr and Decr keys to set
the desired start and stop time and press the Enter key to store the information in the controller. If
the chiller is to be programmed to run continuously 24 hours a day, set the stop tie for 1 minute
before start time (Stop=23:59; Start=00:00). Press the Next Item key to advance through the
remaining week days and Holiday Start/ Stop times.
Menu #21: Holiday Date—Up to 14 holiday dates may be entered. When the MicroTech controller's
current date matches a date set in the holiday schedule, the normal daily start/stop times are
replaced by the holiday start/stop ties which were set in the previous section. At the date prompt, use
the Incr and Decr keys to set the first holiday month and press Enter to advance to the Day position
of the display. Use the lncr, Decr and Enter keys to set the first day of the holiday. Press Next Item to
advance to Holiday 1 Duration. If the scheduled holiday spans more than one day, use the lncr and
Decr keys to set the holiday duration and press Enter to store the information in the controller. Use
the Next Item key to set additional holiday dates and duration’s for the entire year.
Menu#22: Alarm Set Points—On a call for cooling or heating, the controller will open the liquid
line solenoid valve. When the evaporator pressure rises above the Low Pressure Cutin set point, the
first compressor will be started. The Low Pressure cut out set point determines the point at which
the compressors will shut off during a pumpdown sequence. The Refrigerant Freeze and Water
Freeze alarm set points may be adjusted as required. Water and refrigerant freeze alarm time delays
may also be adjusted for this menu. If the condenser High Pressure set point is exceeded, the
controller will shut off the unit.
Menu #23: Miscellaneous Setup—Several general operating characteristic are defined here. These
are set at the factory prior to unit delivery and should not require adjustment. The control software
version number is displayed form this menu. Outdoor air temperature is displayed on Menu 12.
Alarm Menus
Menus 24 through 27 are used to display any alarm conditions which may be present in the unit. All
alarm messages are accompanied by the date and time when the alarm occurred. Important
operating conditions at the time of the alarm are stored in the controller's memory and may be
viewed within the following alarm menus.
Menu #24: Circuit #1 Current Alarm—If refrigerant circuit # 1 is in an alarm condition, the
appropriate alarm message will be displayed here. The temperature and pressure readings at the
time of the alarm will be stored in the controllers memory and may be displayed for analysis from
this menu.
Menu #25: Circuit #2 Current Alarm—If refrigerant circuit #2 is in an alarm condition, the
appropriate alarm message will be displayed here. The temperature and pressure readings at the
time of the alarm will be stored in the controllers memory and may be displayed for analysis from
this menu.
Menu #26: Circuit #1 Previous Alarm—The alarm type for the last recorded circuit #1 alarm may
be displayed from this menu. The time and date at which the previous alarm occurred are also
displayed here. This information will be replaced when a current alarm condition is cleared.
Menu #27: Circuit #2 Previous Alarm—The alarm type for the last recorded circuit #2 alarm may
be displayed from this menu. The time and date at which the previous alarm occurred are also
displayed here. This information will be replaced when a current alarm condition is cleared.