88 AGR 055A through 100A IOMM AGR
Table 48, MENU 23 Misc Setup
Screen Display Factory Setpoint Range
1 Unit Type= Air Cooled
2 Units = English English English - Metric
4 SpeedTrol = No No No - Yes
5 Power = 60 hz 60 60 - 50
6 Port A Baud=xxxx 9600 9600 - 2400 - 1200
7 Pre-Alarm=Blink Blink Blink - Open - Closed
Open
Closed
8 Alarm=Closed Closed Closed - Blink(N/O) - Blink(N/C)
Blink(N/O)
Blink(N/C)
9 OAT Select=None None None - Lcl - Rmt
Lcl
Rmt
10 LvgEvpAdj= 0.0 °F(°C) -0.8 - 0.8 (-0.4 - 0.5)
11 EntEvpAdj= 0.0 °F(°C) -0.8 - 0.8 (-0.4 - 0.5)
12 #1EvpAdj= 0.0psi (kPa) (-13.8 - 13.8)
13 #2EvpAdj= 0.0psi (kPa) (-13.8 - 13.8)
14 #1CndAdj= 0.0psi (kPa) (-13.8 - 13.8)
15 #2CndAdj= 0.0psi (kPa) (-13.8 - 13.8)
16 Refrigerant= R22 Not Changeable
17 Not Changeable
Table 49, MENU 24 #1 Curr Alarm
Screen Display
1 Current Alarm
2 @ 0:00 0/00/00
3 Evap = x.x psi (kPa)
4 Cond = x.x psi (kPa)
5 SuctLine=xxx.x °F(°C)
6 LiquisLn=xxx.x °F(°C)
7 Evap Lvg=xxx.x °F(°C)
8 OAT=xx.xx°F(°C)
9 Capacity= xxx%
10 Fan Stage = x
Table 50, MENU 25 #2 Curr Alarm
Screen Display
1 Current Alarm
2 @ 0:00 0/00/00
3 Evap = x.x psi (kPa)
4 Cond = x.x psi (kPa)
5 SuctLine=xxx.x °F(°C)
6 LiquisLn=xxx.x °F(°C)
7 Evap Lvg=xxx.x °F(°C)
8 OAT=xx.xx°F(°C)
9 Capacity= xxx%
10 Fan Stage = x
Table 51, MENU 26 #1 PrevAlarm
Screen Display
1 1 Current Alarm
2 1 x:xx x/xx/xx
3 2 Current Alarm
4 2 x:xx x/xx/xx
5 3 Current Alarm
6 3 x:xx x/xx/xx
7 4 Current Alarm
8 4 x:xx x/xx/xx
9 5 Current Alarm
10 5 x:xx x/xx/xx
Table 52, MENU 27 #2 PrevAlarm
Screen Display
1 1 Current Alarm
2 1 x:xx x/xx/xx
3 2 Current Alarm
4 2 x:xx x/xx/xx
5 3 Current Alarm
6 3 x:xx x/xx/xx
7 4 Current Alarm
8 4 x:xx x/xx/xx
9 5 Current Alarm
10 5 x:xx x/xx/xx