6.2.11 7 Days Programmable Setting
There are 2 ON/OFF events in one day for the schedule. This schedule is applicable to all the chillers in the network.
<ENTER> <ENTER>
<ESC> <ESC>
<ENTER> <ESC>
Main Menu
Timer Menu
Set Schedule
Summary Pages
Timer 1 Timer 2
ON OFF ON OFF
Sun 0800 1800 - - - - - - - -
Mon 0800 1800 - - - - - - - -
Tue 0800 1800 - - - - - - - -
Wed 0800 1800 - - - - - - - -
Sun
UP or DOWN select day of week. ENTER to select
event or ESC to exit to [Timer Menu].
Timer 1 Timer 2
ON OFF ON OFF
Sun 0800 1800 - - - - - - - -
Mon 0800 1800 - - - - - - - -
Tue 0800 1800 - - - - - - - -
Wed 0800 1800 - - - - - - - -
OFF ON OFF
UP or DOWN select event. ENTER to start setting or
ESC to back to select day of week.
Event setting is same like time setting. User can disable
the event by set it to‘- - - -’
Before the schedule will carry the effect, user need to set ENABLE for “TIMER” in [Timer Menu].
TIMER MENU
Set Time
Set Date
Set Schedule
Timer : Disable
OFF ON OFF
Select “Timer” and press ENTER to start the settings.
UP or DOWN to toggle Enable/Disable, ENTER to
confirm or ESC to cancel.
28

Other manuals for McQuay MAC 100 CR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MAC 100 CR and is the answer not in the manual?

McQuay MAC 100 CR Specifications

General IconGeneral
BrandMcQuay
ModelMAC 100 CR
CategoryChiller
LanguageEnglish

Related product manuals