IM 178 / Page 51
Control parameter record (cont’d)
MENU MENU NAME MENU ITEM =
FINAL
SETTING
13 Clg Control (VAV & CAV-DTC) Set Point = ____ °F ___________
Min OAT = ____ °F ___________
Programs: ART1, ART2, ART3, Min Spt = ____ °F ___________
ART4, ART6 and ART8 Max Spt = ____ °F ___________
Reset = No Reset ___________
Space
Return
OAT
Network
External
Airflow
Min Spt @ = ____ °F ___________
Max Spt @ = ____ °F ___________
Stg Timer = ____ Min ___________
Deadband = ____ °F ___________
Mod Limit = ____ Min ___________
Wait Time = ____ Sec ___________
Max Step = ____ Sec ___________
PA Time = ____ Sec ___________
13 Clg Control (CAV & ZTC) Set Point = ____ °F ___________
Min OAT = ____ °F ___________
Programs: ART5 and ART7 OAT Diff = ____ °F ___________
Min Spt = ____ °F ___________
Max Spt = ____ °F ___________
Stg Timer = ____ Min ___________
Deadband = ____ °F ___________
Mod Limit = ____ °F ___________
Wait Time = ____ Sec ___________
Max Step = ____ Sec ___________
PA Time = ____ Sec ___________
14 Htg Control (VAV & CAV-DTC) Set Point = ____ °F ___________
Max OAT = ____ °F ___________
Programs: ART1, ART2, ART3, Min Spt = ____ °F ___________
ART4, ART6 and ART8 Max Spt = ____ °F ___________
Reset = No Reset ___________
Space
Return
OAT
Network
External
Min Spt @ = ____ °F ___________
Max Spt @ = ____ °F ___________
Stg Timer = ____ Min ___________
Deadband = ____ °F ___________
Mod Limit = ____ °F ___________
Wait Time = ____ Sec ___________
Max Step = ____ Sec ___________
PA Time = ____ Sec ___________
14 Htg Control (CAV-ZTC) Set Point = ____ °F ___________
Max OAT = ____ °F ___________
Programs: ART5 and ART7 Min Spt = ____ °F ___________
Max Spt = ____ °F ___________
Stg Timer = ____ Min ___________
Deadband = ____ °F ___________
Mod Limit = ____ °F ___________
Wait Time = ____ Sec ___________
Max Step = ____ Sec ___________
PA Time = ____ Sec ___________
15 Alarm Limits Hi Supply = ____ °F ___________
Lo Supply = ____ °F ___________
Hi Return = ____ °F ___________
17 Unocc Htg/Clg Cooling Spt = ____ °F ___________
Heating Spt = ____ °F ___________
Continued
(Status Only)
(Status Only)