10 TGZ 040A through TGZ 190A OMM TGZ-1
Table 4, Maximum Fuse Sizing
SINGLE POINT POWER SUPPLY MULTIPLE POINT POWER SUPPLY
WITHOUT EXTERNAL OL'S
WITH EXTERNAL OL'S
TGZ
UNIT
SIZE
VOLTAGE
PHASE
FREQ.
(HERTZ)
WITHOUT
EXTERNAL OL'S
TOTAL UNIT
WITH
EXTERNAL OL'S
TOTAL UNIT
CIRC.#1 CIRC.#2 CIRC.#1 CIRC.#2
208 175 150 110 110 100 100
230 175 125 110 110 90 90
460 90 70 50 50 45 45
040
575
60
60 50 35 35 35 35
208 250 200 150 150 125 125
230 250 200 150 150 110 110
460 110 100 70 70 60 60
050
575
60
100 70 60 60 45 45
208 250 250 175 175 175 175
230 250 250 150 150 150 150
460 125 125 80 80 70 70
060
575
60
110 100 60 60 60 60
208 350 300 225 225 175 175
230 350 250 225 225 150 150
460 150 125 90 90 80 80
080
575
60
125 110 70 70 60 60
208 350 350 225 225 200 200
230 350 300 225 225 200 200
460 175 150 110 110 100 100
100
575
60
125 125 90 90 80 80
208 450 400 225 300 200 250
230 450 350 225 300 200 250
460 200 175 110 125 100 125
110
575
60
175 150 90 110 80 100
208 450 450 300 300 250 250
230 450 400 300 300 250 250
460 225 200 125 125 125 125
120
575
60
175 150 110 110 100 100
208 500 500 300 300 250 250
230 500 450 300 300 250 250
460 250 225 150 150 125 125
150
575
60
200 175 110 110 100 100
208 600 500 300 350 250 350
230 600 500 300 350 250 300
460 250 250 150 175 125 150
170
575
60
225 200 110 150 100 125
208 600 600 350 350 350 350
230 600 500 350 350 300 300
460 300 250 175 175 150 150
190
575
60
350 225 150 150 125 125
NOTE:
1. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA plus 100% of other compressor RLA values.